TECHNICAL
SPECIFICATION for Power-flex series
|
| MODEL |
| 3-7.5 |
3-10 |
3-15 |
3-20 |
3-25 |
3-30 |
3-40 |
3-50 |
3-75 |
3-100 |
|
| Range |
| 7.5 |
10 |
15 |
20 |
25 |
30 |
40 |
50 |
75 |
100 |
|
|
Input
|
|
|
Input Voltage
|
Three phase 415 VAC, 50 Hz nominal
4 Wire & ground
|
|
Input Voltage range
|
355 - 455 VAC
|
|
Input Frequency Range
|
45 - 55 Hz
|
|
Output
|
|
|
Out put voltage
|
1 phase 230V+/-1% or 220V+/- or
110 V +/-1% (only one)* (provide ground)
|
|
Output frequency
|
50 Hz +/- 0.1% or 60 Hz +/- 0.1%
optional
|
|
Output Power factor
|
0.8 lagging to unit
|
|
Inverter
|
|
|
Technology
|
Micro Processor Based High Frequency
PWM, IGBT
|
|
Output over loading
|
100% - continuous & 120% /
150% for 15 mins. / 30 seconds
|
|
Crest factor
|
Better than 3
|
|
Inverter Efficiency
|
> 90%
|
|
THD
|
<2% for liner load & <
3% for nonliner load
|
|
Wave form
|
Pure sine wave
|
|
Transient Response
|
+/- 5% recovers with in 5 msec
for 0 - 100% load
|
|
Power Walk-in
|
20 Secs
|
|
EMI / EMC
|
As per FCC class A
|
|
Noise (audible)
|
< 60 dB at 1 meter
|
|
Charger
|
CVCC type operates in Boost, Float
& Trickle mode
|
|
Battery
|
|
|
Type*
|
SMF, Tubular, Calcium etc.
|
| DC bus |
|
|
Isolation
|
Total lsolation between input
& output for protection against surges &
sags
|
|
Protection
|
Input U/O voltage, Over load,
Short Ckt., DC U/O, Battery Low
|
|
Operating Temp & RH
|
0 - 50° C & 95% (Non Condensing)
|
|
Front Panel display
|
Battery level, Fault diagnostic,
Alarm (LCD Optional)*
|
|
Bypass
|
Static + Manual bypass switch
provided
|
|
Chassis design
|
IP 21
|
|
Cooling
|
Forced Air
|
|
Interface
|
RS-232, SNMP for Windows &
Linux (Optional Feature)*
|