TECHNICAL
SPECIFICATION for Power-flex series
|
| MODEL (Rating KVA) |
|
|
Input
|
|
|
Input Voltage
|
Single phase 230 VAC, 50 Hz nominal
|
|
Input Voltage range
|
170 - 270 VAC
|
|
Input Frequency Range
|
45 - 55 Hz
|
|
Output
|
|
|
Out put voltage
|
1 phase 230V+/-1%
|
|
Output frequency
|
50 Hz +/- 0.1%
|
|
Output Power factor
|
0.8 lagging to unity
|
|
Inverter
|
|
|
Technology
|
High Frequency PWM, IGBT
|
|
Output over loading
|
100% - continuous & 120%/150%
for 15 mins/30 seconds
|
|
Crest factor
|
Better than 3
|
|
Inverter Efficiency
|
> 90%
|
|
THD
|
<2% for linear load, &
<3% for nonlinear load
|
|
Wave form
|
Pure sine wave
|
|
Transient Response
|
+/- 5% recovers with in 5 msec
for 0 - 100% load
|
|
Power Walk-in
|
20 Secs
|
|
EMI / EMC
|
As per FCC class A
|
|
Noise (audible)
|
40 dB at 1 meter
|
|
Charger
|
CVCC type operates in Boost, Float
& Trickle mode
|
|
Battery
|
|
|
Type
|
SMF, Tubular, Calcium etc
|
| DC bus |
|
|
Isolation
|
Total Isolation between input
& output for protection against surges &
sags
|
|
Protection
|
Input U/O, Output U/O voltage,
Over load, Short Ckt, DC U/O
|
|
Operating Temp & RH
|
0 - 50 degree C & 95% (Non
Condensing)
|
|
Front Panel display
|
Battery level, Fault diagnostic,
Alarm (LCD Optional)
|
|
Chassis design
|
IP 21
|
|
Cooling
|
Forced Air
|
|
Bypass
|
Manual bypass switch
|
| Static bypass |
|
|
Communication Interface
|
RS-232, SNMP for Windows optional
|
|